户外60KV隔离开关GW4-66-72.5/1600户外60KV隔离开关GW4-66-72.5/1600户外60KV隔离开关GW4-66-72.5/1600户外60KV隔离开关GW4-66-72.5/1600户外60KV隔离开关GW4-66-72.5/1600户外60KV隔离开关GW4-66-72.5/1600户外60KV隔离开关GW4-66-72.5/1600户外60KV隔离开关GW4-66-72.5/1600

二次绕组之间及剩余电压绕组对地工频耐压一分钟通过3 KV(r.m.s),  通过。

Secondary winding and residual voltage winding to ground frequency withstand voltage one minute through 3kv (r.m.s) , Pass.

补偿电抗器绕组末端对地工频耐压试验一分钟通过10KV(r.m.s),  通过。

Compensation Reactor winding end to ground frequency withstand voltage test one minute through 10 KV (r.m.s) , Pass.

阻尼回路直流电阻测量: 5.0 Ω

DC resistance measurement of damping loop: 5.0

载波耦合装置保护间隙的工频放电电压不大于2KV(r.m.s),(间隙0.5mm左右)

The power frequency discharge voltage of the carrier coupling device protection gap is not more than 2 kv (r.m.s) , (gap is about 0.5 mm)

变压器油:油号DB-45平均击穿电压 >  40KV   ,  通过。

Transformer oil: No. DB-45 average breakdown Voltage > 40KV, Pass.

4、 误差试验Error Test

天气:晴Weather: Sunny

室温:  22 ℃   Room temperature: 22 °C

调节绕组联接方式

Regulating winding connection

X0——X13X11——X22X23——L23L22——L12L13——L0

输  出

端子Output Terminal

负 荷 方 式  VA

cosΦ=0.8  (滞后)

80℅ Un

100℅ Un

120℅ Un

比值差

相角差

比值差

相角差

比值差

相角差

a  n

da  dn

f(℅)

δ(’)

f(℅)

δ(’)

f(℅)

δ(’)

a  n

140

━━

-0.26

+14

-0.26

+10

-0.27

+12

35

━━

+0.32

+3

+0.33

+4

+0.33

+5

5℅ Un

100℅ Un

190℅ Un

f(℅)

δ(’)

f(℅)

δ(’)

f(℅)

δ(’)

da dn

━━

140

+0.40

+32

-0.20

+14

-0.82

+12

━━

35

+0.30

+22

+0.55

+8

+0.78

+42


 